RLSW9 volumetric flow meter for measuring the flow of gases up to 350°C

✅ Volumetric flow and air velocity meter with linear analog output in control quality (0 ... 10 V & 4 ... 20 mA) and switch

✅ Suitable for media temperatures up to 350°C

✅ Measured value display via LCD, LED strip and alarm light

✅ Freely scalable measuring range m/s, m³/h, l/min

✅ Sensitive and fast airflow detection up to 30 m/s, optionally up to 200 m/s

✅ Sensor available in nickel-plated brass (standard), stainless steel or Teflon

✅ Exemplary areas of application: Measurement and control of air flows, building technology, PLC, filter monitoring, extraction and extruder systems, exhaust gases and test benches
  • Detail
  • Parameters
  • 产品手册
  • 使用说明书


  • Medium
    Gases
  • Device type
    Compact flow device
  • Device design
    Compact device including sensor (permanently mounted), Compact device including sensor (remote)
  • Flow range
    0,1 ... 30 m/s (optionally available up to 200 m/s)
  • Flow accuracy
    ±5% of the measuring range end value, Reproducibility ±2% of full scale value
  • Display
    LCD with switchable backlight, Yellow LED for flow velocities > switching point, Green LED during operation, 10 red LEDs for the flow velocity in 10% steps
  • Switching point
    Stepless adjustment (software or potentiometer)
  • Protection class evaluation unit
    IP66
  • Protection class sensor
    IP67
  • Special features
    Linear analog output Flow velocities up to 200 m/s measurable, acknowledgeable alarm, steel housing available on request, adjustable start-up delay 0 ... 300 s Velocity dimensions: m/s, l/min, m³/h, linear analog output can be used up to 350°C media temperature, flow velocities up to 200 m/s measurable, steel housing available on request, acknowledgeable alarm, adjustable start-up delay 0 ... 300 s, velocity dimensions: m/s, l/min, m³/h
  • Output signal
    Switching output, Analog output
  • Switching output specification
    1 NO contact (closes/opens with flow, adjustable)
  • Sensor break output signal
    Fault-specific error codes in the LCD, 4 mA, Relay drops out
  • Sensor short-circuit output signal
    Fault-specific error codes in the LCD, 4 mA, Relay drops out
  • Relay output specification
    1 NO contact (closes/opens with flow, adjustable)
  • Immersion depth
    50, 130, 165, 300, 400, 500, Special lengths on request
  • Process connection
    PG7, optional G1/2-inch, G1/4-inch by means of reducer
  • Housing material
    Polycarbonate, UL94-V0
  • Sensor material
    MS58, nickel-plated (optionally available in stainless steel)
  • Pressure resistance
    10 bar
  • Housing dimensions
    80 mm x 113 mm x 60 mm
  • Power supply
    20 ... 30 V DC
  • Electrical connection
    9 terminals (max. 1.5 mm²)
  • Max. power consumption
    5 VA
  • Current and contact rating
    175 V AC/DC, 0,25 A
  • Minimum switching capacity
    10 mA, 5 V DC
  • Ambient temperature
    -20 ... 60°C
  • Optimal inlet path
    >10 DN
  • Optimal outlet path
    >5 DN
  • Temperature gradient
    30K/min
  • Certificates
    CE
  • ATEX certification
    keine
  • SIL level
    keine
  • Country of origin
    Germany
  • Customs tariff number
    90 26 80 20
  • HS code
    90 26 80


编号
1362F3M8
类型
用于开关柜安装的流量评估装置
插入深度
50/130/165/300/400/500mm
工作电压
24 V DC ±5%, 24 V AC ±5%, 230 V AC ±5%
介质温度
-20 ... 80°C/250°C/350°C
测量范围
0.1 ... 30 m/s或300 m/s
型号
RLSW9
Home
Customer service