Evaluation unit NLSW45-3 Ex, flow monitoring for ATEX areas

✅ Air flow monitor for monitoring air flow in ATEX zones 1 and 2 (optionally also with SIL1 or SIL2 certification)

✅ With switching output (1 NO/ 1 NC) for switch cabinet installation

✅ Type-tested by TÜV NORD in accordance with DIN EN 61010-1: 2011-07

✅ Large measuring range (0.1 ... 30 m/s), quick and easy commissioning

✅ Example areas of application: Monitoring of heating registers, air curtain systems, control dampers, fans, DDC, industrial ovens, granulate dryers
  • Detail
  • Parameters
  • 产品手册
  • 使用说明书


  • Medium
    Gases
  • Device type
    Flow evaluation unit for switch cabinet installation
  • Flow range
    0.1 ... 20 m/s
  • Medium temperature
    0 ... 60°C
  • Display
    LED (voltage & switching point)
  • Switching point
    Stepless adjustment (potentiometer)
  • Protection class evaluation unit
    IP40
  • Special features
    2 Zener barriers included in the scope of delivery , Start-up override 5-60 sec, Additional external start-up override
  • Output signal
    Switching output
  • Switching output specification
    1 changer
  • Sensor break output signal
    Relay drops out
  • Sensor short-circuit output signal
    Relay drops out
  • Relay output specification
    1 changer
  • Housing material
    Polycarbonate glass fiber reinforced (UL94V-0)
  • Housing dimensions
    120 mm x 45 mm x 73 mm
  • Mounting
    DIN rail, to be mounted outside the ATEX zone
  • Power supply
    24 V DC ±5%, 24 V AC ±5%, 230 V AC ±5%
  • Electrical connection
    Terminal strip
  • Max. power consumption
    3 VA
  • Recommended cable cross-section
    2.5 mm²
  • Current and contact rating
    250 VAC, 8 A, 2 kVA
  • Minimum switching capacity
    10 mA, 5 V DC
  • Ambient temperature
    -20 ... 50°C
  • Certificates
    CE, Type-tested by TÜV Nord in accordance with DIN EN 61010-1 2011-07
  • ATEX certification
    II 3G Ex ic IIC T4 Gc, simple electrical equipment; Zone 1
  • SIL level
    none
  • Country of origin
    Germany
  • Customs tariff number
    90 26 80 20
  • HS code
    90 26 80


编号
63377Ex
类型
用于开关柜安装的流量评估装置
工作电压
24 V DC ±5%, 24 V AC ±5%, 230 V AC ±5%
介质温度
0 ...60°C
测量范围
0.1 ... 20 m/s
型号
NLSW45-3 Ex
Home